# CISA adds Ivanti and Zyxel flaws to KEV as refrigeration attacks hit Europe
- URL: https://f4n6.co.uk/security-feed/cisa-adds-ivanti-and-zyxel-flaws-to-kev-as-refrigeration-attacks-hit-europe/
- Published: 2026-11-09T10:18:18.000Z
- Updated: 2026-11-09T10:18:18.000Z
- Author: Jeff Davies
- Tags: #security-feed, CVE-2026-111357, CVE-2026-118527, CVE-2026-107441, CVE-2026-7273, Videostrong Technology, China-nexus espionage group

## 1\. Executive summary

A second wave of attacks on refrigeration controllers ran overnight between 1 and 2 November 2026, reaching at least 10 additional European countries and more than 100 to 115 retail locations, after a first wave overnight between 11 and 12 October 2026 hit approximately 700 supermarkets in France. Unit 42 reports that operators raised unit temperatures as high as 50°C (122°F), that some cases resulted in fires, and that French authorities disclosed refrigeration systems at medical facilities were also affected, with no evidence blood products were spoiled. The initial access vector is unconfirmed; Unit 42 records widespread speculation about vulnerable software versions or manufacturer default credentials, and CISA's 5 November advisory warns of authentication bypass, arbitrary code injection and weak configurations. Separately, CISA added Ivanti Connect Secure flaws CVE-2026-111357 (CVSS 7.0 high, CWE-829) and CVE-2026-118527 (CVSS 4.3 medium, CWE-340) to its Known Exploited Vulnerabilities catalog on 30 October 2026\. For EMEA financial services the refrigeration campaign is a third-party and physical-site exposure rather than a direct one: banks with retail, catering or cold-chain dependencies, and any client operating OT controllers on internet-facing addresses, should treat the exposure data in §3 as the actionable signal.

## 2\. Regulatory framing

| Article                                                        | Trigger (the fact in this item)                                                                                                                                                        | Practical impact                                                                                                                       |
| -------------------------------------------------------------- | -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- | -------------------------------------------------------------------------------------------------------------------------------------- |
| DORA Art. 28: ICT third-party risk, general principles         | Refrigeration controllers at retail and medical sites are operated through equipment providers, and the French Blood Establishment attack targeted a refrigeration equipment provider. | Clients must be able to evidence contractual and monitoring controls over OT and facilities-technology suppliers, not only IT vendors. |
| DORA Art. 29: preliminary assessment of ICT concentration risk | Unit 42 identified over 5,000 internet-exposed devices from manufacturers named in the CERT-FR advisory, indicating a small set of shared device vendors across many sites.            | Where a client's cold-chain or site infrastructure depends on one of those manufacturers, a concentration assessment is due.           |
| NIS2 Art. 21(2)(d): supply chain security measures             | The same shared-vendor exposure applies to essential and important entities operating retail or cold-storage estates.                                                                  | Supply chain security measures must cover facilities and OT suppliers, with assessed and documented risk.                              |

## 3\. Technical analysis & attack chain

Confirmed sequence, from Unit 42's account of public reporting:

1. Operators gained unauthorised access to refrigeration controllers. The access vector is not confirmed in public reporting.
2. Controllers were set to defrost mode, driving unit temperatures as high as 50°C (122°F).
3. The first wave ran overnight between 11 and 12 October 2026 against approximately 700 supermarkets in France.
4. A second wave ran overnight between 1 and 2 November 2026, across at least 10 additional European countries, impacting over 100 to 115 retail locations.
5. Hundreds of supermarkets across the region discarded spoiled food. In some cases the activity resulted in fires.
6. French authorities disclosed that refrigeration systems at medical facilities were also impacted. Unit 42 states there is no evidence blood products were spoiled.

The access vector is the gap that matters. Unit 42 records widespread speculation that affected devices ran vulnerable software versions or used manufacturer default credentials that attackers easily identified, and explicitly labels the vector unconfirmed. CISA's 5 November 2026 advisory warns of potential exploitation via authentication bypass, arbitrary code injection and weak configurations. None of these is established as the entry path for this campaign.

Exposure data from Unit 42's Cortex Xpanse scanning, 5 to 6 November 2026: over 5,000 internet-exposed devices manufactured by companies listed in the CERT-FR advisory from the previous month. Unit 42 cautions that this does not mean those devices run exploitable software versions. For France specifically, exposed devices fell across three periods: 1,853 on 1 to 15 October, 558 on 16 to 31 October, and 316 on 1 to 6 November. The decline is consistent with remediation or disconnection after the first wave; Unit 42 does not attribute a cause.

Attribution is unconfirmed. On 3 November 2026 the pro-Russian hacktivist groups NoName057(16) and Z-Pentest claimed responsibility via Telegram posts, and Unit 42 states those claims remain unverified. A claim by a hacktivist group is the claimant's own assertion. No MITRE ATT&CK profile exists for either group in the reference data used for this advisory, and no nation-state tasking is established by any source.

The Ivanti items are a separate event and are covered here only because CISA added them in the same week. CVE-2026-111357 carries CVSS 7.0 high, CWE-829 (inclusion of functionality from an untrusted control sphere), EPSS 1%, and was added to CISA KEV on 30 October 2026\. CVE-2026-118527 carries CVSS 4.3 medium, CWE-340, EPSS 1%, and was added to KEV the same day. CISA's direction to federal agencies to remediate followed Ivanti updating an earlier security advisory with details about the flaws. The specific vulnerable and fixed Ivanti Connect Secure versions are not stated in public reporting available here.

A third item in the same weekly roundup is unrelated to either event and is noted only to prevent confusion: Binarly found that Zyxel GS1900 switches patched for CVE-2026-7273 (CVSS 8.8 high, CWE-121, in CISA KEV since 21 September 2026, EPSS 3%) remained exploitable via CVE-2026-107441 (CVSS 8.8 high, CWE-787, not in KEV, EPSS 0%), because the patch closed a different bug from the one the exploit relies on.

## 4\. Mitigation & containment

P1, within 24 hours:

- Inventory every refrigeration, HVAC and cold-storage controller reachable from the internet or from a flat corporate network. Unit 42's Xpanse data shows over 5,000 such devices exposed across Europe; a client that has not enumerated its own estate cannot know whether it appears in that population.
- Remove direct internet exposure from controller management interfaces. Where remote access is contractually required, place it behind an authenticated broker and restrict source addresses.
- Replace manufacturer default credentials on every controller and change shared site passwords. Default credentials are the leading speculation for the access vector, and CISA's advisory names weak configurations.
- For Ivanti Connect Secure, apply Ivanti's updated advisory guidance for CVE-2026-111357 and CVE-2026-118527\. Both are in CISA KEV with a 30 October 2026 addition date. No fixed version numbers are stated in the reporting available here; obtain them from Ivanti directly.

P2, within 72 hours:

- Set controller temperature and defrost parameters so that a remote command cannot drive a unit above a safe ceiling without a local physical confirmation, and enable alerting on defrost cycles initiated outside maintenance windows.
- Confirm that fire detection and suppression coverage extends to refrigeration plant rooms. Unit 42 reports fires resulted from some attacks.
- Ask facilities and cold-chain suppliers named in the CERT-FR advisory list whether their devices are internet-exposed, and require written confirmation of default-credential removal.

P3, within 7 days:

- Add OT and facilities-technology suppliers to the third-party register with the concentration analysis DORA Art. 29 requires where one manufacturer dominates the estate.
- Rehearse the manual fallback for cold-chain monitoring so that loss of controller telemetry does not also mean loss of temperature visibility.

## 5\. Indicators of compromise

No indicators of compromise available in the source material.

Neither Unit 42 nor the weekly roundup publishes file hashes, domains, IP addresses or controller command strings for this campaign. The sources describe behaviour rather than atomic artefacts, so the table below records behaviour only. There is no copyable indicator block.

### Behavioural indicators

| behaviour                                                                                                                    | where to observe                                                                            | confidence                                               |
| ---------------------------------------------------------------------------------------------------------------------------- | ------------------------------------------------------------------------------------------- | -------------------------------------------------------- |
| Refrigeration controller setpoints or mode changed to defrost outside a maintenance window                                   | Controller configuration logs, BMS/SCADA audit trail, setpoint history                      | High, reported by Unit 42                                |
| Unit temperature driven toward 50°C (122°F)                                                                                  | Cold-room temperature telemetry and alarm history                                           | High, reported by Unit 42                                |
| Authentication to a controller management interface from an unexpected source address or with a manufacturer default account | Controller and BMS authentication logs, network flow records to controller management ports | Medium, access vector unconfirmed                        |
| Simultaneous defrost activation across multiple sites in a short window                                                      | Central monitoring platform, cross-site alert correlation                                   | Medium, inferred from the overnight timing of both waves |

## 6\. Detection

Insufficient indicators to author detection rules.

The sources give no file artefacts, command strings, process names, registry keys or network values for this campaign. A YARA or Sigma rule built from the available material would match reporting about the attacks rather than the attacks themselves.

## CVE assessment

4 referenced CVEs — **3 actively exploited (CISA KEV)**

| CVE                                                                                | CVSS       | Exploited        | EPSS | Summary                                                                                                                          |
| ---------------------------------------------------------------------------------- | ---------- | ---------------- | ---- | -------------------------------------------------------------------------------------------------------------------------------- |
| [CVE-2026-7273](https://nvd.nist.gov/vuln/detail/CVE-2026-7273?ref=f4n6.co.uk)     | 8.8 High   | ⚠ KEV 2026-09-21 | 3%   | A stack-based buffer overflow vulnerability in the CGI program of Zyxel GS1900-48HPv2 firmware versions through 2.90(ABTQ.1)C0…  |
| [CVE-2026-111357](https://nvd.nist.gov/vuln/detail/CVE-2026-111357?ref=f4n6.co.uk) | 7.0 High   | ⚠ KEV 2026-10-30 | 1%   | Ivanti Connect Secure 22.8R2.4 mishandles the manner in which the dsinvoked broker trusts DSCache configuration data, leading t… |
| [CVE-2026-118527](https://nvd.nist.gov/vuln/detail/CVE-2026-118527?ref=f4n6.co.uk) | 4.3 Medium | ⚠ KEV 2026-10-30 | 1%   | Use of predictable filenames in Ivanti Connect Secure before versions 25.1.1.3 and 22.8R2.6 allows a remote authenticated attac… |
| [CVE-2026-107441](https://nvd.nist.gov/vuln/detail/CVE-2026-107441?ref=f4n6.co.uk) | 8.8 High   | —                | 0%   | An out-of-bounds write vulnerability in the CGI program of Zyxel GS1900-24E firmware versions through 2.90(AAHK.2)C0 could allo… |

## 7\. Sources

- Help Net Security, "Week in review: Refrigeration cyberattacks hit European retailers again, Patch Tuesday forecast", 2026-11-08\. https://www.helpnetsecurity.com/2026/11/08/week-in-review-refrigeration-cyberattacks-hit-european-retailers-again-patch-tuesday-forecast/
- Palo Alto Unit 42, "Turning Up the Heat: Inside the Attacks on Europe's Refrigeration System". https://unit42.paloaltonetworks.com/europes-refrigeration-systems-attacks/

## 8\. Adverse Trace position

Adverse Trace assesses the refrigeration campaign as a high-impact availability attack on OT with an unconfirmed access vector and unverified hacktivist attribution; the Ivanti KEV additions are a separate, verified exploitation state and are rated at the CVSS values recorded above, 7.0 high and 4.3 medium. Client impact for EMEA financial services is indirect but concrete: cold-chain and facilities suppliers, retail banking premises with food service, and any estate with internet-exposed controllers carry the exposure, and the 5,000-device figure from Unit 42 means the population is large enough that a supplier's assurance cannot be taken on trust. The NoName057(16) and Z-Pentest claims are single-sourced to Telegram and unverified by Unit 42; treat them as claims, not attribution. We will track CERT-FR and CISA updates for a confirmed access vector and for Ivanti fixed-version guidance, and we will reissue this advisory if either is published. Clients should send us their controller inventory and supplier list so we can check them against the exposed-device population.

---

[Read the original source →](https://www.helpnetsecurity.com/2026/11/08/week-in-review-refrigeration-cyberattacks-hit-european-retailers-again-patch-tuesday-forecast/?ref=f4n6.co.uk)

*Published via PulseTrace — Adverse Trace threat intelligence.*